ICS Commercial Calculator Suite 2-115+ Tons Coverage
Calculators
6 ToolsSystem Range
2-115+ TonsCompliance
ASHRAE 62.1Analysis
ROI FocusedTXV Sizing Calculator
TRY IT NOWPurpose: Verify TXV sizing for commercial refrigeration systems
Capacity: 24,000 BTU/hr to 1,500,000+ BTU/hr (2-125+ tons)
Key Features:
- Commercial refrigerant calculations (R-410A, R-22, R-134a, R-407C)
- Pressure drop analysis for large systems
- Prevents floodback in large commercial units
- Real-time sizing validation
Airflow Calculator
/airflowcalcPurpose: Quick airflow estimation for commercial systems
Capacity: All commercial sizes
Key Features:
- Standard CFM = BTU/hr ÷ (1.08 × ΔT) calculations
- Commercial CFM per ton analysis (350-575 CFM/ton range)
- Static pressure evaluation for commercial ductwork
- R-22 aging system analysis for large installations
Commercial Airflow Diagnostic
/airflowdiagnosticPurpose: Advanced diagnostic engine for comprehensive commercial analysis
Capacity: 2-115+ tons with size-specific thresholds
Advanced Features:
- Commercial-Specific Diagnostics: Different algorithms for all system sizes
- Code Compliance Checking: ASHRAE 62.1 ventilation requirements
- Business Impact Analysis: Cost calculations, payback periods
- Application-Specific Standards: Office, retail, healthcare, manufacturing
- Commercial Cost Analysis: Energy costs, demand charges
Commercial Subcool Calculator
/subcoolcalcPurpose: Precision refrigerant charge analysis for commercial systems
Capacity: 2-115+ tons with size-specific diagnostic thresholds
Commercial Refrigerant Support:
Standard commercial
Legacy systems
Chiller applications
R-22 replacement
High efficiency (A2L)
Low GWP (A2L)
Advanced Features:
- Bubble Point Calculation with accurate P-T relationships
- Commercial Diagnostics with charge level assessment (60-130%)
- Performance Impact Analysis with capacity/efficiency loss calculations
- Business Impact Analysis with annual energy cost calculations
- System Health Scoring (0-100% overall condition)
- Professional Diagnostic Categories (Critical/Performance/Normal)
Refrigerant P-T Calculator
/rptcalcPurpose: Professional pressure-temperature lookup for field diagnostics and design calculations
Capacity: 14 commercial refrigerants with bidirectional conversion capabilities
Core Functionality:
Pressure → Temperature
Field diagnostic mode - most common use caseTemperature → Pressure
Design/calculation mode for system planningSmart Interpolation Engine:
Exact
Direct data point matchInterpolated
Linear calculation between pointsExtrapolated
Outside normal range - warningProfessional Features:
- Real-time calculation with immediate updates
- PSIG/PSIA conversion handling
- System type tracking (RTU, Split, Chiller, etc.)
- Capacity documentation and application notes
- Safety classifications (A1/A2L) and GWP awareness
- Operating range validation (-48°F to 120°F)
Wet Bulb to Enthalpy Calculator NEW
/wbenthalpyPurpose: Psychrometric conversions for field measurements and design verification
Range: 35°F to 85°F wet bulb temperature with 510 precise data points
Bidirectional Conversion:
Wet Bulb → Enthalpy
Field measurements mode - convert sensor readingsEnthalpy → Wet Bulb
Design verification mode - confirm specificationsEnhanced Psychrometric Calculations:
Components
Components
Temperature
Grains/lb
Data Quality Indicators:
Exact Match
Direct data point detectionInterpolated
Linear interpolation with error estimatesExtrapolated
Out-of-range warningsProfessional Features:
- Interpolation Engine: 510 data points (35°F to 85°F in 0.1°F increments)
- Psychrometric Formulas: Industry-standard calculations for all air properties
- Auto-calculation: Smooth UX with immediate results on valid input
- System Context: Measurement location tracking and equipment integration
- Operating Analysis: Intelligent notes based on wet bulb ranges
- Capacity Calculations: Total cooling capacity and SHR when applicable
Small Commercial (2-10 tons)
Applications: Small offices, retail shops, restaurants
350-450 CFM/ton
0.8-1.5" WC
$1,200
Basic commercial analysis with residential-like simplicity
Medium Commercial (10-30 tons)
Applications: Medium offices, retail stores, schools
375-525 CFM/ton
1.0-2.0" WC
$1,000
Enhanced analysis with zone considerations
Large Commercial (30-75 tons)
Applications: Large offices, hospitals, shopping centers
400-550 CFM/ton
1.5-2.5" WC
$900
Complex system analysis with economizer and VAV support
Industrial (75+ tons)
Applications: Manufacturing, large warehouses, data centers
425-575 CFM/ton
2.0-3.0" WC
$800
Advanced analysis with process-specific requirements
Subcool Ranges by System Type
System Type | Optimal Range | Characteristics |
---|---|---|
Packaged Rooftop Unit | 8-18°F | Standard commercial cooling |
Air Cooled Chiller | 5-12°F | Precise temperature control |
Water Cooled Chiller | 4-10°F | High efficiency operation |
Heat Pump | 6-16°F | Dual mode operation |
Process Cooling | 10-20°F | Industrial applications |
Data Center Cooling | 8-16°F | Reliable operation critical |
Supermarket Refrigeration | 12-25°F | Large refrigerant charges |
Industrial Refrigeration | 15-30°F | High capacity systems |
Airflow Standards by Application
Application | CFM/Person | CFM/Sq Ft | Typical Occupancy |
---|---|---|---|
Office Building | 20 | 0.06 | 100 sq ft/person |
Retail | 15 | 0.12 | 30 sq ft/person |
Restaurant | 20 | 0.18 | 70 sq ft/person |
Manufacturing | 20 | 0.50 | 500 sq ft/person |
Warehouse | 20 | 0.05 | 2000 sq ft/person |
Healthcare | 25 | 0.18 | 120 sq ft/person |
Static Pressure Guidelines by Size
System Size | Normal Range | Maximum | Warning Level |
---|---|---|---|
2-10 tons | 0.8-1.2" WC | 1.5" WC | 1.3" WC |
10-30 tons | 1.0-1.5" WC | 2.0" WC | 1.7" WC |
30-75 tons | 1.2-2.0" WC | 2.5" WC | 2.2" WC |
75+ tons | 1.5-2.5" WC | 3.0" WC | 2.7" WC |
P-T Chart Reference & Refrigerant Properties
Sample P-T Data Points (Common Temperatures)
Refrigerant | 32°F (PSIG) | 70°F (PSIG) | 105°F (PSIG) | 130°F (PSIG) |
---|---|---|---|---|
R-410A | 103.5 | 201.4 | 363.9 | 504.1 |
R-22 | 43.0 | 120.9 | 241.9 | 345.0 |
R-134A | 9.9 | 70.8 | 142.4 | 205.0 |
R-32 | 69.1 | 170.2 | 331.9 | 469.4 |
Refrigerant Categories & Safety Classifications
Refrigerant | Safety Class | GWP | Common Application | Status |
---|---|---|---|---|
R-410A | A1 | 2088 | Standard commercial AC | Current |
R-22 | A1 | 1810 | Legacy systems | Phaseout |
R-134A | A1 | 1430 | Chillers | Transitioning |
R-32 | A2L | 675 | High efficiency systems | Emerging |
R-454B | A2L | 466 | R-410A replacement | Future |
Psychrometric Reference Data
Typical Wet Bulb Temperature Ranges
Condition | Wet Bulb (°F) | Enthalpy (BTU/lb) | Application |
---|---|---|---|
Winter Design | 35-45 | 15-20 | Heating load calc |
Spring/Fall | 50-65 | 21-28 | Economizer operation |
Summer Design | 70-78 | 31-38 | Cooling load calc |
Extreme Summer | 79-85 | 39-45 | Peak load conditions |
Common Measurement Locations
Return Air
Typical: 75°F DB, 62°F WB, 26.5 BTU/lbOutside Air (Summer)
Design: 95°F DB, 78°F WB, 38.1 BTU/lbSupply Air
Typical: 55°F DB, 53°F WB, 21.8 BTU/lbMixed Air
Variable: Based on OA/RA mix ratioKey Psychrometric Relationships
Enthalpy Formula
h = 0.240 × DB + W × (1061 + 0.444 × DB)
Where: h = enthalpy (BTU/lb), DB = dry bulb (°F), W = humidity ratio
Cooling Capacity
Q = CFM × 4.5 × Δh
Where: Q = BTU/hr, Δh = enthalpy difference
Refrigerant Cost Analysis
Refrigerant | Cost/lb | Category | Service Cost Range |
---|---|---|---|
R-410A | $12.50 | Standard | $350 - $6,000 |
R-22 | $45.00 | Expensive | $525 - $6,000 |
R-454B | $35.00 | New Tech | $525 - $6,000 |
R-134a | $15.00 | Chiller | $350 - $3,750 |
Common Issues by Size
Small Commercial (2-10 tons)
- Similar to residential but higher capacity
- Focus on filter maintenance and basic airflow
- Simple economizer systems if present
Medium Commercial (10-30 tons)
- Multi-zone considerations
- Economizer complexity increases
- Static pressure becomes more critical
- Demand charge considerations
Large Commercial (30-75 tons)
- Complex ductwork systems
- VAV considerations
- Code compliance critical
- Energy management focus
- Professional maintenance required
Industrial (75+ tons)
- Process-specific requirements
- High static pressure systems
- Specialized filtration needs
- Peak demand management critical
- Planned maintenance essential